E 101 Indoor unit communication error(1min.) • Check the communication line for indoor units • Check the power supply of the communication phase(DC) 1 Time Operation-off
E 102 Communication time-out error(2min.) • Check the communication line for indoor units • Check the power supply of the communication phase(DC) 1 Time Operation-off
E 121 Indoor temperature sensor • Check the temp. sensor of the indoor unit room • Check the indoor PCB connector 1 Time Operation-off
E 122 Indoor unit EVA IN sensor • Check the indoor unit drainage pipe sensor • Check the indoor PCB connector 1 Time Operation-off
E 123 Indoor unit EVA OUT sensor • Check the indoor unit drainage pipe sensor • Check the indoor PCB connector 1 Time Operation-off
E 128 Dismount of indoor unit EVA IN sensor • Check the drainage pipe has been dismounted 1 Time Operation-off
E 129 Dismount of indoor unit EVA OUT sensor • Check the drainage pipe has been dismounted 1 Time Operation-off
E 153 Secondary detection of indoor floating switch • Check the indoor unit's float sensor • Check the indoor PCB connector 1 Time Operation-off
E 154 Indoor fan error • Check the indoor PCB connector 1 Time Operation-off
E 162 Indoor eeprom error • Check the EEPROM data • Check the indoor's option 1 Time Operation-off
E 163 Indoor eeprom option error • Check the EEPROM data • Check the indoor's option 1 Time Operation-off
E 201 Indoor unit not connected • Check the indoor unit connection • Check the indoor unit number(multi only) 1 Time Operation-off
E 202 1min. Time out Comm. (Display Board : Onboard : Indoor ↔ Outdoor) • Check the indoor unit connection • Check the indoor unit option 1 Time Operation-off
E 203 Abnormal Serial communication(Display Board: Indoor ↔ Outdoor) - - -
E 221 Outdoor temp sensor error (Dual/Single) • Check the connection status of the sensor • Check the sensor location • Check the risistance values of sensor 1 Time Operation-off
E 237 Cond temp sensor error (Dual/Single) • Check the connection status of the sensor • Check the sensor location • Check the risistance values of sensor 1 Time Operation-off
E 251 Discharge temp sensor error (Dual/Single) • Check the connection status of the sensor • Check the sensor location • Check the risistance values of sensor 1 Time Operation-off
E 416 Discharge over temperature (Dual/Single) - 3 Times Operation-off
E 440 Operation condition secession(HEATING) • Check the operation status of operation mode • Check the temp. sensor 1 Time Operation-off
E 441 Operation condition secession(COOLING) • Check the operation status of operation mode • Check the temp. sensor 1 Time Operation-off
E 458 Fan error • Check the input power connection status • Check the connection status between the motor and PCB in outdoor unit • Check the fuse of indoor/outdoor units 1 Time Operation-off
E 461 Comp Starting error • Check the connection status of the compressor • Check the resistand between different phases in compressor 5 Time Operation-off
E 462 I_Trip error / PFC Over current • Check the input power • Check the refrigerant is filled • Check the outdoor fan operation normally 3 Time Operation-off
E 464 IPM Over Current(O.C) • Check the refrigerant is filled • Check the connection status of compressor and if it operates normally • Check for any obstacles around indoor/outdoor units 9 Time Operation-off
E 465 Comp Vlimit error • Check the connection status of compressor • Check the resistance between different phases in compressor 9 Times Operation-off
E 466 DC-Link voltage under/ over error • Check the connection of input power - Restart(after 3min.)
E 467 Comp rotation error • Check the connection status of the compressor • Check the resistance between different phases in compressor 3 Times Operation-off
E 468 Current sensor error • Check the PCB operates normally 1 Times Operation-off
E 469 DC-Link valtage sensor error • Check the connection of input power 1 Times Operation-off E 471 OTP error • Check the PCB operates normally 1 Times Operation-off
E 472 AC Line Zero Cross Signal out • Check the connection of input power 1 Times Operation-off
E 473 Comp Lock error • Check the connection status of the compressor • Check the resistance between different phases in compressor 3 Times Operation-off
E 475 Fan error(two fan outdoor • Check the input power connection status • Check the connection status between the motor and PCB in outdoor unit • Check the fuse of indoor/outdoor units 1 Times Operation-off
E 554 GAS Leak error(Dual/Single) • Check refrigerant is filled • Check the indoor EVA sensor 3 Times Operation-off
E 556 Capacity miss match • Check the indoor unit's option code • Check the capacity of indoor unit's and outdoor unit's 1 Times Operation-off